Belted cable ( Multi core cable )

  • The multi core cable is used for voltage rating up to 11,000 V. 
  • It is belted type cable consists of circular shaped / oval shaped / sector shaped. 
  • Each core of multi core cable is wrapped by impregnated paper insulation. 
  • The space between core / conductor is filled with packing to make the cable circular cross section. 
  • There is insulating belt of impregnated paper is provided surrounding all the cores. 
  • The impregnated paper is covered by lead sheath in order to protect paper against moisture. 

belted-cable


Why belted cable is not used above 22 kV?

  • The belted type cable construction is not suitable for voltage rating above 22 kV because of radial and tangential stress development in the cable. 
  • The tangential stress acts along the insulation. 
  • The electric resistance, dielectric strength of the impregnated paper is higher across the layer than along the layer. 
  • The leakage current causes power loss due to tangential stress along the impregnated paper insulation and it may be breakdown it. 
  • As cables are belted together, one / two core of the cable is over stress whereas remaining core is under stress under loading and unloading condition. 
  • This may result in formation of voids between cores. 
  • The spaces between cores are ionized during loading of cable and it may deteriorate cable insulation. 
  • In order to protect insulation against leakage current, screened cables are used in which leakage current is earthed through metallic screen. 